Three-phase unidirectional transformerless hybrid rectifier with boost converter
Loading...
Files
Date
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE Global Power, Energy and Communication Conference — GPECOM2019
Abstract
In this paper, a three-phase hybrid rectifier is proposed, employing a boost converter without the addition of
isolation transformer and output voltage control. This topology is usually considered to be not viable due to the current interactions. In order to mitigate those interactions, the boost inductor is
replaced by a magnetically coupled inductor. The coupled inductor forces the balance between the two interconnected
windings, placed at the positive and negative poles, and thus eliminating the current interactions. The results show that the proposed three-phase rectifier does not undergo a current interaction and functions as a hybrid rectifier. Furthermore, it was noted that the proposed rectifier at 20 kW presents an elevated power factor and a low total harmonic distortion.